9 | Electrical installation
Installer reference guide
129
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
7
9
YCY2
X2M
12
3
A4P
1+2 Wires connected to the space
cooling/heating ON/OFF output
3 Wire between X2M and A4P
A4P Installation of EKRP1HBAA is
required.
A
Y27
B
A
B
7 9
X2M
A4P
Y2YC
X1M
ab
a Installation of EKRP1HBAA is required.
b Prewiring between X2M/7+9 and Q1L (=thermal protector backup heater). Do NOT
change.
3 Fix the cable with cable ties to the cable tie mountings.
9.3.8 To connect the changeover to external heat source
INFORMATION
Bivalent is only possible in case of 1 leaving water temperature zone with:
room thermostat control, OR
external room thermostat control.
Wires: 2×0.75mm²
Maximum load: 0.3A, 250VAC
Minimum load: 20mA, 5VDC
[9.C] Bivalent