10 | Configuration
Installer reference guide
168
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
# Code Description
[1.6] [2-0A] Room sensor offset (user interface used as
room thermostat): Offset on the actual room
temperature measured by the user interface
used as room thermostat.
▪ –5°C~5°C, step 0.5°C
[1.7] [2-09] Room sensor offset (external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
▪ –5°C~5°C, step 0.5°C
Room comfort setpoint
Restriction: Only applicable if:
▪ Smart Grid is enabled ([9.8.4]=Smart grid), and
▪ Room buffering is enabled ([9.8.7]=Yes)
If room buffering is enabled, the extra energy from photovoltaic panels is buffered
in the DHW tank and in the space heating/cooling circuit (i.e. heat up or cool down
the room). With the room comfort setpoints (cooling/heating) you can modify the
maximum/minimum setpoints that will be used when buffering the extra energy in
the space heating/cooling circuit.
# Code Description
[1.9.1] [9-0A] Heating comfort setpoint
▪ [3-07]~[3-06]°C
[1.9.2] [9-0B] Cooling comfort setpoint
▪ [3-09]~[3-08]°C
10.6.3 Main zone
Overview
The following items are listed in the submenu: