8 | Piping installation
Installer reference guide
95
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
If the total liquid piping
length is…
Then…
≤10m Do NOT add additional refrigerant.
>10m R=(total length (m) of liquid piping⁠–⁠10m)×0.020
R=Additional charge (kg) (rounded in units of
0.01kg)
INFORMATION
Piping length is the one-way length of liquid piping.
8.4.4 To determine the complete recharge amount
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
8.4.5 To charge additional refrigerant
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
If pump down is needed in case of dismantling or relocating the system, see
"15.2To pump down"[4263] for more details.
8.4.6 To fix the fluorinated greenhouse gases label
1 Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate

Table of Contents