Daikin Altherma ERGA04E V3 Series - To Connect the Safety Thermostat (Normally Closed Contact)

Daikin Altherma ERGA04E V3 Series
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 | Electrical installation
Installer reference guide
131
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
2 Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.
1245
S6S
S7S
S8S
S9S
3
A
B
A
B
A8P
X801M
a
1 2 3 4 5
a Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
9.3.10 To connect the safety thermostat (normally closed contact)
Wires: 2×0.75mm²
Maximum length: 50m
Safety thermostat contact: 16VDC detection (voltage supplied by PCB).
The voltage-free contact shall ensure the minimum applicable load of
15VDC, 10mA.
1 Open the following (see "7.2.4To open the indoor unit"[471]):
1 Top panel
1
2
3
2 User interface panel
3 Upper switch box cover
2 Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.
Note: The jumper wire (factory-mounted) must be removed from the respective
terminals.