13 | Maintenance and service
Installer reference guide
250
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
6 Open the valve on the bottom of the water filter to drain water from the
water circuit. Collect the drained water in a bottle, sink,… using the installed
drain hose.
7 Remove the 2 clips that fix the water filter.
a
b
a
a Clip
b Magnetic filter/dirt separator
8 Remove the water filter.
9 Remove the drain hose from the water filter.
NOTICE
Although the water circuit is drained, some water may be spilled when removing the
magnetic filter/dirt separator from the filter housing. ALWAYS clean up spilled water.
13.5.2 To clean the water filter in case of trouble
1 Remove the water filter from the unit. See "13.5.1 To remove the water
filter"[4249].
NOTICE
To protect the piping connected to the magnetic filter/dirt separator from damage it
is recommended to perform this procedure with the magnetic filter/dirt separator
removed from the unit.
2 Unscrew the bottom of the water filter housing. Use an appropriate tool if
needed.
NOTICE
Opening the magnetic filter/dirt separator is ONLY required in case of severe issues.
Preferably this action is never to be done during the complete lifetime of the
magnetic filter/dirt separator.
a
b
a Bottom part to be unscrewed
b Water filter housing
3 Remove the strainer and the rolled‑up filter from the water filter housing and
clean with water.