6 | Application guidelines
Installer reference guide
50
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
6.4.3 Setup and configuration – DHW tank
▪ For large DHW consumptions, you can heat up the DHW tank several times
during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature, you can use the
following energy sources:
- Thermodynamic cycle of the heatpump
- Electrical backup heater
▪ For more information about optimizing the energy consumption for producing
domestic hot water, see "10Configuration"[4138].
6.4.4 DHW pump for instant hot water
Setup
a Cold water IN
b Hot water OUT (shower (field supply))
c DHW pump (field supply)
d Recirculation connection
▪ By connecting a DHW pump, instant hot water can be available at the tap.
▪ The DHW pump and the installation are field supply and the responsibility of the
installer. For the electrical wiring, see "9.3.5To connect the domestic hot water
pump"[4126].
▪ For more information about connecting the recirculation connection, see
"8.6.5To connect the recirculation piping"[4109].
Configuration
▪ For more information, see "10Configuration"[4138].
▪ You can program a schedule to control the DHW pump via the user interface. For
more information, see the user reference guide.