EasyManua.ls Logo

Daikin Altherma ERGA04E V3 Series - Page 180

Daikin Altherma ERGA04E V3 Series
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 | Configuration
Installer reference guide
180
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
# Code Description
[3.4] N/A Setpoint mode:
Fixed
WD heating, fixed cooling
Weather dependent
Heating WD curve
Set weather-dependent heating for the additional zone (if [3.4]=1 or 2):
# Code Description
[3.5] [0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
Note: There are 2 methods to set the weather
dependent curve. See "10.5.22-points
curve"[4159] and "10.5.3Slope-offset
curve"[4160]. Both curve types require 4 field
settings to be configured according to the figure
below.
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
T
t
: Target leaving water temperature
(additional zone)
T
a
: Outdoor temperature
[0-03]: Low outdoor ambient temperature.
40°C~+5°C
[0-02]: High outdoor ambient temperature.
10°C~25°C
[0-01]: Desired leaving water temperature
when the outdoor temperature equals or drops
below the low ambient temperature.
[9‑05]°C~[9‑06]°C
Note: This value should be higher than [0‑00]
as for low outdoor temperatures warmer water
is required.
[0-00]: Desired leaving water temperature
when the outdoor temperature equals or rises
above the high ambient temperature.
[9‑05]~min(45, [9‑06])°C
Note: This value should be lower than [0‑01] as
for high outdoor temperatures less warm water
is required.
Cooling WD curve
Set weather-dependent cooling for the additional zone (if [3.4]=2):

Table of Contents

Related product manuals