Troubleshooting by Remote Controller ESIE15-13B
150 Service Diagnosis
4.19 Discharge Pipe Temperature Control
Remote
Controller
Display
F3
Applicable
Models
RZQG
Method of Error
Detection
The error is detected according to the temperature detected by the discharge pipe temperature
sensor.
Error Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
When the discharge pipe temperature does not rise after operation start
Supposed
Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor
Refrigerant shortage
Defective compressor
Disconnection of discharge pipe thermistor
Defective outdoor unit PCB