ESIE15-13B Field Setting from Remote Controller
Field Setting 73
2.4 Overview of the Field Setting on the Outdoor Units
Remote
controller
settings
The table below contains the remote controller settings.
Factory settings The table below contains the factory settings of all outdoor units
Mode
No.
First
Code
No.
Description Second Code No. Details
01 02 03 04 05
16 (26)
0 Night time low
noise operation
Disabled
(Factory
setting)
Automatic
low noise
activation
Capacity
preceding
setting
(when
using
KRP58
option)
Automatic
low noise +
capacity
preceding
— Refer to
P74.
1 Automatic low
noise start and
stop time
— — 22h00 ~
06h00
22h00 ~
08h00
(Factory)
20h00 ~
08h00
Refer to
P74.
2EDP room
setting
Disabled
(Factory
setting)
— EDP room
setting
EDP room
setting +
no freeze
up
— Refer to
P77.
3 Defrost starting
setting
Standard
(Factory
setting)
Defrost
slow
starting
setting
Defrost
quick
starting
setting
— — Refer to
P80.
7Slow start for
EDP
applications
Normal
start
Slow start — — —
Mode No. First Code No. Second Code No.
26
001
104
201
301
701