ESIE15-13B Troubleshooting by Remote Controller
Service Diagnosis 133
4.11 Malfunction of Motion Sensor / Floor Temperature
Sensor
Remote
Controller
Display
CE
Applicable
Models
Indoor unit: FXYFP~B
Method of Error
Detection
Detect by a signal outputted from the sensor.
Error Decision
Conditions
When malfunction is detected by a signal outputted from the sensor.
Supposed
Causes
Disconnection of connector from or failure of motion sensor [CE-01]
Failure of floor temperature sensor (wiring disconnection in temperature compensation
circuit) [CE-02]
Failure of floor temperature sensor (wiring disconnection in temperature compensation
circuit) [CE-03]
Failure of floor temperature sensor element [CE-04]
Troubleshooting
Go to Diagnosis Flowchart-1.
Go to Diagnosis Flowchart-2.
Go to Diagnosis Flowchart-3.
Go to Diagnosis Flowchart-4.
The contents of individual failures
vary with detailed malfunction code.
Ensure the detailed malfunction code,
and then go to the relevant Diagnosis
Flowchart.
Detailed malfunction code
CE-01
Detailed malfunction code
CE-02
Detailed malfunction code
CE-03
Detailed malfunction code
CE-04

Table of Contents

Other manuals for Daikin FAQ71CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71CVEB and is the answer not in the manual?

Daikin FAQ71CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ71CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals