ESIE15-13B Field Setting from Remote Controller
Field Setting 67
2.3 Settings Contents and Code No. for Indoor Units
You can change the setting of 3 x 3 sensing cassette as mentioned below
The method of field setting, which can be conducted through remote controller, is
established practice, but it is possible only with BRCE52 remote controller.
Mode
No.
First
Code
No.
Description of Setting
Second Code No.
01 02 03 04 05
10
(20)
0
Filter
cleaning
sign
interval
Long life
filter
2,500 hrs. 1,250 hrs.
1 Filter type Long Super long
2
Remote controller
thermistor
Enabled Disabled
3 Filter cleaning sign Display No display
7
(note 4)
Detection time for NOT
presence
30 min 60 min
8
(note 5)
Compensation of
suction air temperature
in heating mode
COMPENSATE
(Temperature
[A+2] °C which an
air conditioner
controls when the
temperature of a
remote controller
is A °C)
NO
COMPENSATION
(Temperature [A]
°C which an air
conditioner
controls when the
temperature of a
remote controller
is A °C)
——
11
(21)
2
Fan OFF at Thermostat
OFF
Normal OFF
3
Airflow rate setting
during heating
Standard Slightly up Up
4
Automatic operation
mode control
Available Prohibition
6
(note 6)
Sensitivity of presence
sensor
High Low Standard
Sensor does
not work
11
(22)
0 Option (KRP1B*) output Compressor Option Operation Malfunction
7
(note 6)
Compensation of
temperature around
human body
Floor sensor does
not work
Higher priority on
the air
temperature
Standard
Higher
priority on
the floor
temperature
8
(note 6)
Compensation of floor
temperature
-4°C -2°C ±0°C +2°C
12
(22)
3
Fan speed heating
thermostat OFF
LL-speed Set-speed
5
Automatic restart after
power failure reset
Disabled Enabled
6
Fan speed cooling
thermostat OFF
LL-speed Set-speed
13
(23)
0
High air outlet velocity
(for high ceiling
applications)
Standard Slightly up Up
1
Selection of airflow
direction
4-way flow 3-way flow
2
Flap moving in the
swing mode
All 4 flaps
synchronized
Two opposite
flaps
synchronized
——
4 (*2) Airflow range setting Upper Normal Lower

Table of Contents

Other manuals for Daikin FAQ71CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71CVEB and is the answer not in the manual?

Daikin FAQ71CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ71CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals