EasyManuals Logo

Daikin FAQ71CVEB Service Manual

Daikin FAQ71CVEB
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Function Details ESIE15-13B
38 Function and Control
3.2.6 Room Thermostat Control
Based on the difference between the set temperature by remote controller and indoor unit
suction air temperature, the thermo. is turned on and off.
ΔT = Indoor suction air temperature – temperature set by remote controller (Cooling)
ΔT = Temperature set by remote controller – indoor suction air temperature (Heating)
Thermostat ON Condition
ΔT > +0.5°C
Thermostat OFF Condition
or
•&
• ∆T
– 0.5°C continues for 1 minute
• 5 minutes or more after start up
• ∆T
– 2°C (Cooling)
• ∆T
– 2.5°C (Heating)
When changed suddenly from ∆T
+1.5°C to ∆T
-0.5°C

Table of Contents

Other manuals for Daikin FAQ71CVEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71CVEB and is the answer not in the manual?

Daikin FAQ71CVEB Specifications

General IconGeneral
BrandDaikin
ModelFAQ71CVEB
CategoryAir Conditioner
LanguageEnglish

Related product manuals