Troubleshooting SiUS04-924_A
Service Diagnosis 105
4.23 Refrigerant Shortage
Remote
Controller
Display
U0
Method of
Malfunction
Detection
Refrigerant shortage detection I:
Refrigerant shortage is detected by checking the input current value and the compressor running
frequency. If the refrigerant is short, the input current is lower than the normal value.
Refrigerant shortage detection II:
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends to
rise.
Refrigerant shortage detection III:
Refrigerant shortage is detected by checking the difference between suction and discharge
temperature.
Malfunction
Decision
Conditions
Refrigerant shortage detection I:
The following conditions continue for 7 minutes.
Input current
A × output frequency + B
Output frequency > C
Refrigerant shortage detection II:
The following conditions continue for 80 seconds.
Opening of the electronic expansion valve D
Discharge pipe temperature (°C) > E × target discharge pipe temperature (°C) + F (°C)
(Discharge pipe temperature (°F) > E × target discharge pipe temperature (°F) + G (°F))
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of discharge pipe thermistor, indoor or outdoor heat exchanger thermistor, room
or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective electronic expansion valve
A
(–) B (A) C (Hz)
27/1000 2.0 40
D (pulse) E (–) F (°C) G (°F)
Cooling
480 128/128
50 90
Heating 45 81