SiUS04-924_A Main Functions
24 Function and Control
1.11 Inverter POWERFUL Operation
Outline To optimize the cooling and heating capacity, operate the air conditioner by increasing the indoor
fan rotating speed and the compressor frequency.
Detail When the POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
A = 50 rpm
Ex.): POWERFUL operation in cooling mode.
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C (64.4°F)
DRY Dry rotating speed + A rpm Lowered by 2.5°C (4.5°F)
HEAT H tap + A rpm 31.5°C (88.7°F)
FAN H tap + A rpm
AUTO Same as cooling / heating in
POWERFUL operation
The target temperature is
kept unchanged.
(R13571)
Target temp.
Fan
A rpm
18˚C (64.4˚F)
H tap
Set tap
20 minutes
It should be the lower limit of
cooling temperature.
It counts 20 minutes. also
in the remote controller.
POWERFUL
ON
POWERFUL
OFF
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Operation OFF
3. POWERFUL operation is OFF.