SiUS04-924_A Indoor Unit
150 Removal Procedure
5
Remove the motor
mounting plate.
Reassembling the fan motor
When reassembling the fan
rotor, provide as much as
5 mm (0.2 inch) of play between
the side face of the rotor and the
bottom frame.
(1) Insert the fan motor with approx.
5 mm (0.2 inch) left.
(2) Tighten the screw until it stops.
Then turn the screw in one
scroll.
(3) Move the fan rotor and confirm
the fan motor and the fan rotor
are installed appropriately.
(4) Tighten the screw completely if
appropriate.
(5) If not appropriate, go back to
(1).
When reassembling, engage
the vibration absorber
completely.
6
Remove the fan motor.
7
Remove the vibration
absorber.
Step
Procedure Points
(R9564)
Motor mounting plate
(R14472)
Side face of rotor
Side face of
bottom frame
5 mm
(0.2 inch)
(R9566)
Vibration