EasyManuals Logo
Home>Daikin>Air Conditioner>FTYN35DV3B ATY35DV2

Daikin FTYN35DV3B ATY35DV2 User Manual

Daikin FTYN35DV3B ATY35DV2
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
SiBE01-503 Troubleshooting
Service Diagnosis 65
4.7 Thermistor or Related Abnormality (Outdoor Unit)
Remote
Controller
Display
J6
Method of
Malfunction
Detection
This type of error is detected by checking the thermistor input voltage to the microcomputer.
[A thermistor error is detected by checking the temperature.]
Malfunction
Decision
Conditions
The thermistor input is above 4.96 V or below 0.04 V with the power on.
Outdoor heat exchanger thermistor: above about 100°C (less than 670
Ω)
Supposed
Causes
Connector in poor contact
Thermistor defective
Indoor unit PCB defective

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTYN35DV3B ATY35DV2 and is the answer not in the manual?

Daikin FTYN35DV3B ATY35DV2 Specifications

General IconGeneral
BrandDaikin
ModelFTYN35DV3B ATY35DV2
CategoryAir Conditioner
LanguageEnglish

Related product manuals