Installation and operation manual
10
FWEC2
Advanced electronic controller
FC66002764
Push the keys at the same time
Use the keys to change the value on the display
until arriving at the password for self-diagnosis (030) and
press .
The following screen will be displayed:
Press the
button to switch on the various thermostat
outputs in sequence.
Symbol Actuation Terminals
Extra low speed N-V0
Min. speed N-V1
Med. speed N-V2
Max. speed N-V3
Valve N-Vc
Electrical heater
Second valve
N-Vh
no symbol no active outlet
The electronic controller outputs can be checked one by
one either by observing the respective component (valve,
fan..) or verifying whether a voltage of 230 V is present at the
corresponding terminals.
To exit the self-diagnosis procedure press
(after a
few minutes the thermostat will automatically exit in any
case).
DESCRIPTION OF READ/WRITE REGISTERS [R/W]
“Digital 1” REGISTER:
H
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8
En.Vel
En.Min/
Max
En.Set En.MinT En.ECO En.RE En.S/W
En.On/
Off
L
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
- - Lock MinT Eco RE S/W On/Off
- On/Off: On/Off via supervision system
- S/W: Mode set via supervision system (0: Cooling, 1:
Heating)
- RE: selection of electrical heater via supervision system
- Eco: Economy mode ON via supervision system
- MinT.: Minimum Temperature control ON via supervision
system
- Lock: keypad lock (0: unlocked, 1: locked)
- En.On/Off :enabling of On/Off control via supervision
system
- En.S/W: enabling of mode control via supervision system
- En.RE: enabling of selection of electrical heater function
via supervision system
- En.ECO: enabling of economy mode activation via supervi-
sion system
- En.MinT: enabling of selection of Minimum Temperature
logic via supervision system
- En.Set: enabling of forced override of setpoint via supervi-
sion system
- En.Min/Max: enabling of setpoint thresholds via supervi-
sion system
- En.Vel: enabling of selection of fan speed via supervision
system
“SETPOINT - COOLING” Register: setpoint imposed by
supervision system for the Cooling mode
“SETPOINT - HEATING” Register: setpoint imposed by
supervision system for the Heating mode
“MINIMUM SETPOINT - COOL.” Register : lower limit
for setpoint in cooling mode
“MAXIMUM SETPOINT - COOL.” Register “: upper limit
for setpoint in cooling mode
“MINIMUM SETPOINT - HEAT.” Register “: lower limit
for setpoint in heating mode
“MAXIMUM SETPOINT - HEAT.” Register “: upper limit
for setpoint in heating mode
“SPEED” Register: selection of fan speed via supervision
system
“ECONOMY CORRECTION” Register: correction of set-
point in the case of economy mode imposed by supervisor
(this correction is an amount subtracted from or added to
the setpoint, based on the operating mode)
SELF-DIAGNOSIS PROCEDURE
This procedure allows you to check whether the individual
outputs of the controller function correctly.
To run the procedure, follow the directions below:
Switch the thermostat off
001 level:
password entry