4. If the outdoor temperature decreases, the setpoint is lowered up to 68°F by the Sliding
Temperature function.
When the room temperature further decreases to 60°F, this function changes the
operation mode to Heat. At that time, the setpoint becomes 60°F. At the beginning,
heating was started with setpoint at 68°F, however, the setpoint became 60°F as a result
of the change heat
cool
heat.
2. When this function is simultaneously used with the schedule and interlocking control functions,
this function may not work as intended with the settings.
Example: When the method for referencing room temperature and setpoint is set up to Fixed and
the thermal difference to 7°F
1. Heating starts with setpoint for the indoor unit reference of indoor temperature and
setpoint set at 68°F.
2. The operation mode of that indoor unit is changed to Cool using the remote controller.
3. When the room temperature becomes 68°F or higher, the operation mode of the indoor
unit of the Auto Changeover group is changed to Cool and the setpoint set to 68°F. If the
operation mode had not been changed using the remote controller, the indoor unit works
in Heat mode until the room temperature becomes 75°F, and the setpoint should have
changed to 75°F when the operation mode changed to Cool but it didn’t.