User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
125
6-4 Setting up Maintenance and Checking
You can set a specic management point to “maintenance” or release it from “maintenance”.
A management point set to “maintenance” cannot be controlled from the iTM, that is, it cannot
receive input signals such as orders of operation, automatic control, status monitoring, etc.
However, emergency stop is possible.
The following describes how to set this function up.
1. Touch the Maintenance button on the System Settings tab of the Menu List screen and display
the Maintenance Settings screen (see page 54).
(2) (1)
2. To set to maintenance, select a management point from (1) and touch the Add button to move it
to (2). The management point is set to maintenance. Touch the OK button to save and close the
screen.
3. To release from maintenance, select a management point from (2) and touch the Remove button
to move it to (1). The management point is released from maintenance.
When nished, touch the OK button to save and close the screen.