User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
304
iTM Monitoring Control Functions
Setting location Number of settings
Central
Monitoring
Area Number of areas that can be created Up to 650 (All excluded)
Total number of management points
that can be registered in areas
Up to 1300
Number of management points that
can be registered in one area
Up to 650
Number of hierarchical levels Up to 10
Management point
* The total of all management points
is 650.
Indoor unit management point Up to 512
Outdoor unit management point Up to 80
External management point Up to 512
(Total of External management point,
BACnet management point and
Internal.Ai)
BACnet management point
Unit’s port management point Up to 32
Internal Pi management point Up to 80
Layout View screen Number of images that can be used
in a layout
Up to 60
Number of icons that can be placed
in one image
Up to 100
History Number of records that can be saved Up to 100,000 (iTM)
Up to 10,000 (iTM integrator)
*
Including the number of internal
development records. The internal
development records cannot be viewed.
Automatic
Control function
Schedule function Number of schedule programs Up to 100
Number of schedule patterns Weekly: 7 patterns
Special day: 5 patterns
Number of events Up to 20 per schedule
Yearly calendar Calendar view 1 year
Maximum number of calendars that
can be registered
40
Interlocking Control function Number of interlocking programs Up to 500
Number of management points that
can be used as input
Up to 50
Number of events for Output1 Up to 25
Number of events for Output2 Up to 25
Emergency Stop function Number of emergency stop
programs
Up to 32
(Including the Default program)
Number of management points that
can be registered in one group
Up to 650
Number of management points that
can be used in an emergency stop
signal
Up to 6
Auto Changeover function Number of groups that can be
created
Up to 512
Number of management points that
can be registered in one group
Up to 64
Temperature Limit function Number of groups that can be
created
Up to 8
Number of management points that
can be registered in one group
Up to 512
Sliding Temperature function Number of groups that can be
created
Up to 8
Number of management points that
can be registered in one group
Up to 512
Number of Ai management points
that can be registered in one group
Up to 1
HMO function Number of management points that
can be controlled with HMO
Up to 512
Timer Extension function Timer Extension times Selectable from 30 Min, 60 Min,
90 Min, 120 Min, 150 Min, 180 Min