User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
120
Saving and loading the area data CSV le
You can save the area settings in a USB memory as a CSV le (AreaData.csv). You can also load a
CSV le from a USB memory. Make sure the le is named “AreaDate.csv” as it is the only readable
fail name.
(18)
(19)
1. To save, connect a USB memory to the iTM unit and touch the Save button (18) on the Area
Setup screen. A conrmation dialog with the message “Do you want to save area data in CVS
format? Max Time: 15 sc” will appear. Touch the Yes button to save. When successfully saved,
the message “File has been saved. will appear.
2. To load, connect the USB memory with the CSV le le in the iTM unit and touch the Load button
(19) on the Area Setup screen. A conrmation dialog with the message “Loaded data will delete
existing data. Max Time: 15 sc” will appear. Touching the Yes button will start loading the data.
When the CSV le to load is corrupt, an error screen is displayed. Correct the errors sequentially
from the top.
The format of the CSV le used for saving and loading Area Data is as follows.
[File version]
@S:AREA-INFO
S
A, [Area ID], [Area name] ,[Detailed information],[Starting Interval.] ,[Stopping Interval.],[Icon ID]
, A, [Area ID], [Area name] ,[Detailed information] ,[Starting Interval.] ,[Stopping Interval.] ,[Icon ID]
, , P, [Management point ID]
, P, [Management point ID]
• • •
@E:AREA-INFO
@S:PNT-INFO
[Management point ID], [Management point name], [Management point’s detailed information], [Management point type],[Icon ID]
• • •
@E:PNT-INFO
(1) Area information block
(2) Management point information block