Interlocking Control Restrictions
Handling of communication error
The input condition is either a “valid” or “invalid” status of the target (input management point).
When a communication error occurs, the status is handled as “unfixed” because it cannot be
assessed. The changes in a status before and after “unfixed” (“valid (invalid)
unfixed” or
“unfixed
valid (invalid)”) are not considered triggers of cleared conditions. However, a valid
status change is treated as trigger if it occurred before becoming “unxed” or after returning from
“unxed.
Handling of start
The initial status of a target (input management point) when started is handled as “unfixed”.
Similarly to the case above, the changes in status before and after “unxed” are not viewed as
triggers of success.
Handling of maintenance
This function does not work when the management point target of condition detection or control
is in maintenance.
Inconsistent settings
The system will not output any warning even if an inconsistent or inadequate setting is specied
for this function. Be sure to carefully check by yourself before using.
Condition cleared immediately after program setup
If the input changes while the program is being edited or when toggling from disabled to enabled,
a condition may be considered cleared depending on the timing. Do not change settings when
input is about to change.