User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
157
Timing-dependent interlocking control
In cases where two inputs change simultaneously, for example, the function may temporarily
work unexpectedly depending on the timing.
Example:
Setting example
Program 1, Input: 1-00, 1-01, Output 1: At least one input becomes valid
1-02 On
Program 1, Input: 1-00, 1-01, Output 2: inputs become valid
1-02 Off
Input
ON
ON
When input 1-00 and input 1-01 simultaneously change from OFF to ON,
the controller may detect two statuses as indicated in the figure below.
Output 1-02 ON Output 1-02 OFF
Temporarily outputs ON
Status (2)Status (1)
1-00
1-01
ON
OFF
If another condition is cleared while the interlocking control for an already cleared condition is
being executed, the latter does not trigger any interlocked control.
Example: When the required condition is “Any turned ON”, control is executed as indicated in the
gure below.
Input 1
OFF
ON
ON
Input 2
OFF
OFF
ON
Input 3
OFF
OFF
ON
Interlocking Control Yes
Interlocking Control No
Time