User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
161
(11)
(10)
(12)
Check that the Output1 tab (10) is displayed and
Select “At least one input becomes valid” in the Input condition combo box (11).
The step above nishes the setup of the required conditions, “which is either indoor unit “a”
or “b” to be On for 10 minutes”.
4. Setting up the target
Touch the Modify button (12) and display the Interlock Program Output Setup screen.
(14)
(15)
(13)
(13) is the list of management points and areas that can be registered.
Select Ventilator “c” and touch the Add button to register it as target of the output event in (14).
5. Setting up the output actions
Select the Ventilator “c” registered in (14) and touch the Action Setup button (15). The Action
Setup screen appears.