User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
91
• When changing the date setting of iTM
If the time setting of iTM is changed and the date setting is accordingly changed, pre-cool/heat
already scheduled on the changed date will be ignored and the normal schedule will be
executed.
• When restarting iTM
If iTM is restarted, pre-cool/heat scheduled on the day of restart will be ignored and the normal
schedule will be executed.
• Execution of pre-cool/heat during 0:00 to 2:59
If you set pre-cool/heat to be executed during 0:00 to 2:59, the pre-cool/heat setting will be
ignored and the normal schedule will be executed.
• When the daylight saving time starts or ends
Pre-cool/heat may not be executed or may be executed twice depending on the time setting.
• When using an air conditioner without changeover option
Even if you set pre-cool/heat to an air conditioner without changeover option, the setting will
be executed according to the operation mode of an air conditioner with changeover option.
(6) Stop radio button
Select to stop the target.
(7) Setback High, Setback Low radio buttons
Select either of the two radio buttons when setting up the Setback function.
These radio buttons are displayed only when the optional Setback function is enabled.
(8) OK button
Saves the edit and closes the screen.
(9) Cancel button
Cancels the edit and closes the screen.