Operating Instructions BD Controller 101N07xx Series 24 V DC
20
DEHC.PS.100.I.02
4.2.8 Compressor safety
In order to prevent the compressor from short cycling a minimum restart time is built in.
After timeout of Compressor restart time a new start of the compressor is permitted.
Settings
4.2.9 Communication
Lost communication
InanetworksystemwithcustomdesignedinterfacemodulesactingasmasterontheModbus,itis
desirable to stop the compressor from running when communication to the master is lost.
If communication is lost it will not be possible for the customer to stop the compressor as long as cool-
ing is requested.
Thefunctionwillstopthecompressorafteracertaintime,(Communication time out) when there is no
contacttothemastercontroller.ThestopisrealizedthroughtheMainSwitch. The Main Switch will be
set to OFF. It will remain OFF until the master controller sets it back to ON via Modbus.
Protection of settings
A coded privacy function protects customers’ settings from being read by third parties.
The code must be verified by entering twice.
Settings
Name Default Max value Min value Step Unit
Compressor
restart time
60 120 60 1 Seconds
Name Default Max value Min value Step Unit
Node number 1 247 1 1 -
Bits per second 19200 19200 9600 9600
0=Disabled
1=Enabled
Communication 0 1 0 1 Seconds
Communication
timeout
900 7200 15 1 -
Setting protection
code & status
0 9999 0 1 -

Other manuals for Danfoss 101N0715

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 101N0715 and is the answer not in the manual?

Danfoss 101N0715 Specifications

General IconGeneral
BrandDanfoss
Model101N0715
CategoryController
LanguageEnglish

Related product manuals