VLT
®
MICRO
Avoid loose wiring and possible shorts. Tighten all screws on AC circuit terminals
securely.
It is a good practice to maintain a 90° angle between wires connected to the AC
circuit terminals and wires connected to the control terminals.
Use shielded cables for Control Circuit wiring,
Use conduit for the AC power line. The conduit on both the input and output of the
power line should be grounded.
If an EMI filter is required, it should be located close to the drive. Reducing carrier
frequency can also be a way to reduce EMI noise, however audible noise from the
motor will increase.
An L-Filter can be added to the U.V.W. side of AC Motor Drives if needed. Do not use
a Capacitor, or L-C Filter (Inductance-Capacitance), or R-C Filter (Resistance-
Capacitance).
A “Ground Fault Interrupt Circuit” can be used. To avoid malfunctioning of the motor
and drive, sensitivity of the current sensor should not be less than 200 mA with a
response time not less than 0.1 second.