VLT
®
MICRO
3.3 ADR (1, 0)
00: Broadcast to all AC drives ARD1 = 30Hex, ADR0 = 30Hex
01: To AC drive at Address 01 ARD1 = 30Hex, ADR0 = 31Hex
0F: to AC drive at Address 0F ARD1 = 30Hex, ADR0 = 46Hex
10: To AC drive at Address 10 ARD1 = 31Hex, ARD0 = 30Hex
Maximum is 254, at Address FE
3.4 CMD (1, 0)
CMD0:
"0" 30Hex: Stop
"1" 31Hex: FWD + RUN
"2" 32Hex: REV + RUN
"3" 33Hex: JOG + FWD + RUN
"4" 34Hex: JOG + REV + RUN
"5" 35Hex: E.F. ON (External Fault)
"6" 36Hex: Reset
"7" 37Hex: Write Parameter
"8" 38Hex: Read Parameter
"9" 39Hex: Read Inverter Status
"A" 41Hex: Reserved
"B" 42Hex: Reserved
"C" 43Hex: Reserved
"D" 44Hex: Reserved
"E" 45Hex: Reserved
"F" 46Hex: Reserved
CMD1:
Bit 0 = 0 No Mirror Telegram
Bit 0 = 1 Mirror Telegram
Bit 2 = 1 When Bit 2 = 1, Means CEXX; clear with RESET command
86