EasyManuals Logo
Home>Danfoss>Temperature Controller>ECL 2000

Danfoss ECL 2000 Installation Guide

Danfoss ECL 2000
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
Application 10
EI.65.D4.02
79
ECL 2000 Type 2:
The motor valve M3 controls the storage tank temperature, which is measured by
the sensor S6. During tank heating, M3 performs PI regulation of the return tem-
perature in the hot-water circuit measured by S11. Because of the delay caused by
the storage tank and the return temperature control, the integral action must be dis-
abled. The circulation pump P3 is controlled according to the 7-day program.
Use the controller’s service menu to set the parameter
Integr. time to 0. This disables the integral action.
Appendix C of this Guide provides an overview of the
service menus. The ECL 2000 User’s Guide (ref. [2])
provides detailed instructions for operating the service
menus.

Table of Contents

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals