Magnetic and electromagnetic elds generated near the current-carrying conductors and permanent magnets in electric
machines represent a health danger to persons with heart pacemakers, metal implants and hearing aids. Persons with a
heart pacemaker, metal implants or hearing aids must consult a doctor before they enter the following areas:
Areas in which electric equipment and parts are operated.
Areas in which electric equipment with permanent magnets are stored, mounted, operated or repaired.
Risk of electric shock when working with the electric machine. Use isolated electric tools.
Only trained and qualied personnel familiar with the relevant safety requirements can
work with
the electric machine.
Use correct
personal protective equipment when you are
near the electric machine.
Read the instructions in this
manual before you install
the electric machine.
Required tools
Following tools are required to install the electric machine:
Ratchet torque wrench.
Hex head wrench kit with different metric sizes.
Socket wrench kit with different metric sizes.
Lifting slings with lifting eyes (with sufficient rated capacity) . Size according to machine type.
Insulation resistance test
Do not touch the electric machine during the
insulation resistance check
.
Discharge the machine afterwards.
Measure the insulation resistance of the electric machine before and after installation of the
electric machine. Because of the structure of the electric machine it is possible that the stator is
damaged during the installation.
The reference value of
150 M
Ω
must
be exceeded in room
temperature. Contact Danfoss representative if the reference value is not exceeded.