0-20 Display Line 1.1 Small
Option: Function:
[1603] Status Word Present status word
[1605] Main Actual
Value [%]
View the two-byte word sent with the
Status word to the bus Master reporting
the Main Actual Value.
[1609] Custom
Readout
View the user-defined readouts as
defined in par. 0-30 Custom Readout Unit,
par. 0-31 Custom Readout Min Value and
par. 0-32 Custom Readout Max Value.
[1610] Power [kW] Actual power consumed by the motor in
kW.
[1611] Power [hp] Actual power consumed by the motor in
HP.
[1612] Motor Voltage Voltage supplied to the motor.
[1613] Frequency Motor frequency, i.e. the output frequen-
cy from the frequency converter in Hz.
[1614] Motor Current Phase current of the motor measured as
effective value.
[1615] Frequency [%] Motor frequency, i.e. the output frequen-
cy from the frequency converter in
percent.
[1616] Torque [Nm] Present motor load as a percentage of
the rated motor torque.
[1617] Speed [RPM] Motor speed reference. Actual speed will
depend on slip compensation being
used (compensation set in par. 1-62 Slip
Compensation). If not used, actual speed
will be the value read in the display
minus motor slip.
[1618] Motor Thermal Thermal load on the motor, calculated
by the ETR function. See also parameter
group 1-9* Motor Temperature.
[1622] Torque [%] Shows the actual torque produced, in
percentage.
[1626] Power Filtered
[kW]
[1627] Power Filtered
[hp]
[1630] DC Link
Voltage
Intermediate circuit voltage in the
frequency converter.
[1632] Brake Energy /s Present brake power transferred to an
external brake resistor.
Stated as an instantaneous value.
[1633] Brake Energy /
2 min
Brake power transferred to an external
brake resistor. The mean power is
calculated continuously for the most
recent 120 seconds.
[1634] Heatsink Temp. Present heat sink temperature of the
frequency converter. The cut-out limit is
0-20 Display Line 1.1 Small
Option: Function:
95 ± 5° C; cutting back in occurs at 70 ±
5° C.
[1635] Inverter
Thermal
Percentage load of the inverters
[1636] Inv. Nom.
Current
Nominal current of the frequency
converter
[1637] Inv. Max.
Current
Maximum current of the frequency
converter
[1638] SL Controller
State
State of the event executed by the
control
[1639] Control Card
Temp.
Temperature of the control card.
[1643] Timed Actions
Status
[1650] External
Reference
Sum of the external reference as a
percentage, i.e. the sum of analog/pulse/
bus.
[1652] Feedback
[Unit]
Reference value from programmed
digital input(s).
[1653] Digi Pot
Reference
View the contribution of the digital
potentiometer to the actual reference
Feedback.
[1654] Feedback 1
[Unit]
View the value of Feedback 1. See also
par. 20-0*.
[1655] Feedback 2
[Unit]
View the value of Feedback 2. See also
par. 20-0*.
[1656] Feedback 3
[Unit]
View the value of Feedback 3. See also
par. 20-0*.
[1658] PID Output [%] Returns the Drive Closed Loop PID
controller output value in percent.
[1660] Digital Input Displays the status of the digital inputs.
Signal low = 0; Signal high = 1.
Regarding order, see par. 16-60 Digital
Input. Bit 0 is at the extreme right.
[1661] Terminal 53
Switch Setting
Setting of input terminal 53. Current = 0;
Voltage = 1.
[1662] Analog Input
53
Actual value at input 53 either as a
reference or protection value.
[1663] Terminal 54
Switch Setting
Setting of input terminal 54. Current = 0;
Voltage = 1.
[1664] Analog Input
54
Actual value at input 54 either as
reference or protection value.
[1665] Analog Output
42 [mA]
Actual value at output 42 in mA. Use
par. 6-50 Terminal 42 Output to select the
variable to be represented by output 42.
[1666] Digital Output
[bin]
Binary value of all digital outputs.
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
66 MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
7