FC 300 Profibus
How to Control the FC 300
Bit 09, Local operation/bus control
Bit 09 = "0" means that [STOP/RESET] is activated on the control unit, or that Local control in par. 3-13
Reference site is selected. It is not possible to control the frequency converter via serial communication.
Bit 09 = "1" means that it is possible to control the frequency converter via the fieldbus/ serial communication.
Bit 10, Out of frequency limit
Bit 10 = "0", if the output frequency has reached the value in par. 4-11 Motor speed low limit or par.
4-13 Motor speed high limit.
Bit 10 = "1" means that the output frequency is within the defined limits.
Bit 11, No operation/in operation
Bit 11 = "0" means that the motor is not running.
Bit 11 = "1" means that the frequency converter has a start signal or that the output frequency is greater
than 0 Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12 = "0" means that there is no temporary over temperature on the inverter.
Bit 12 = "1" means that the inverter has stopped because of over temperature, but that the unit has not
tripped and will resume operation once the over temperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13 = "0" means that there are no voltage warnings.
Bit 13 = "1" means that the DC voltage in the frequency converter’s intermediate circuit is too low or too high.
B
it 14, Torque OK/limit exceeded
Bit 14 = "0" means that the motor current is lower than the torque limit selected in par. 4-16 Torque limit
motor mode or par. 4-17 Torque limit generator mode.
Bit 14 = "1" means that the torque limit in par. 4-16 and 4-17 has been exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15 = "0" means that the timers for motor thermal protection and VLT thermal protection, respectively,
have not exceeded 100%.
Bit 15 = "1" means that one of the timers has exceeded 100%.
39
MG.33.C2.02 - VLT is a registered Danfoss trademark

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Profibus and is the answer not in the manual?

Danfoss FC 300 Profibus Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Profibus
CategoryDC Drives
LanguageEnglish

Related product manuals