FC 300 Profibus
Troubleshooting
LED 1: Net Status
Phases Bi-colour LED Status
Red The PROFIBUS card is defect.
Contact Danfoss Drives
Power On
Green The PROFIBUS card is OK.
Search baud
rate
Green Searching for the baud rate. Chec k the
connection to the master if it stays in
this state.
Green Baud rate found - waiting for parameters
from the master.
Wait
Parameterizing
Red Wrong parameters from the master.
Green Parameters from master OK - waiting
for configuration data.
Wait
Configuration
Red Wrong Configuration data from the
master.
Green Data Exchange between the master and
the FC 300 is active.
Data Exchange
Red Clear State. Warning 34 is active and a
bus reaction in par. 8-04 is executed.
LED 2: Module Status
Bi-colour LED Status
No light No PROFIBUS DPV1 communication is active.
Green DP V1 communication from a Master Class 1 (PLC) is active.
Green DPV1communicationfromaMasterClass2(MCT10,FDT)
is active.
Green DP V1 communication from a Master Class 1 and 2 is active.
Red Internal error.
76
MG.33.C2.02 - VLT is a registered Danfoss trademark

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Profibus and is the answer not in the manual?

Danfoss FC 300 Profibus Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Profibus
CategoryDC Drives
LanguageEnglish

Related product manuals