Function Setting
4-30 Motor
Feedback Loss
Function [1] Warning
4-31 Motor
Feedback Speed
Error
100 RPM
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start
Event
[19] Warning
13-02 Stop
Event
[44] Reset
key
13-10 Comparat
or Operand
[21] Warning
no.
13-11 Comparat
or Operator
[1] ≈*
13-12 Comparat
or Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL digital
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The SLC
monitors Warning 90 and in
the case that Warning 90
becomes TRUE then Relay 1 is
triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 s then the frequency
converter continues and the
warning disappears. But Relay 1
will still be triggered until
[Reset] on the LCP.
Table 6.13 Using SLC to Set a Relay
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB841.10
Function Setting
5-40 Function
Relay
[32] Mech.
brake ctrl.
5-10 Terminal 18
Digital Input
[8] Start*
5-11 Terminal 19
Digital Input
[11] Start
reversing
1-71 Start Delay 0.2
1-72 Start
Function
[5] VVC
plus
/
FLUX
Clockwise
1-76 Start
Current
I
m,n
2-20 Release
Brake Current
App.
dependent
2-21 Activate
Brake Speed
[RPM]
Half of
nominal slip
of the motor
*=Default Value
Notes/comments:
Table 6.14 Mechanical Brake Control
Start (18)
Start
reversing (19)
Relay output
Speed
Time
Current
1-71
1-71
2-21
2-21
1-76
Open
Closed
130BB842.10
Illustration 6.4 Mechanical Brake Control
Application Examples
VLT
®
AutomationDrive Operating
Instructions
48 MG33AM02 - VLT
®
is a registered Danfoss trademark
66

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
EnclosureIP20
ApprovalscUL, UL, CE
EMC filterBuilt-in
Communication OptionsCANopen, PROFIBUS DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Output Voltage0-100% of supply voltage