P5K5 P7K5 P11K
High/ Normal Load
1)
HO NO HO NO HO NO
Typical Shaft Output [kW] 5.5 7.5 7.5 11 11 15
Enclosure IP20 B3 B3 B4
Enclosure IP21 B1 B1 B2
Enclosure IP55, IP66 B1 B1 B2
Output current
Continuous (3x200-240 V) [A] 24.2 30.8 30.8 46.2 46.2 59.4
Intermittent (60 s overload)
(3x200-240 V) [A]
38.7 33.9 49.3 50.8 73.9 65.3
Continuous kVA (208 V AC) [kVA] 8.7 11.1 11.1 16.6 16.6 21.4
Max. input current
Continuous (3x200-240 V) [A] 22 28 28 42 42 54
Intermittent (60 s overload)
(3x200-240 V) [A]
35.2 30.8 44.8 46.2 67.2 59.4
Additional specifications
IP21 max. cable cross-section
5)
(mains, brake,
load sharing) [mm
2
(AWG)]
2)
16,10, 16 (6,8,6) 16,10, 16 (6,8,6) 35,-,- (2,-,-)
IP21 max. cable cross-section
5)
(motor) [mm
2
(AWG)]
2)
10,10,- (8,8,-) 10,10,- (8,8,-) 35,25,25 (2,4,4)
IP20 max. cable cross-section
5)
(mains, brake,
motor and load sharing)
10,10,- (8,8,-) 10,10,- (8,8,-) 35,-,- (2,-,-)
Max. cable cross-section with Disconnect [mm
2
(AWG)]
2)
16,10,10 (6,8,8)
Estimated power loss
at rated max. load [W]
4)
239 310 371 514 463 602
Weight,
enclosure IP21, IP55, IP66 [kg]
23 23 27
Efficiency
4)
0.964 0.959 0.964
Table 10.2 Mains Supply 3x200-240 V AC
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG33AM02 - VLT
®
is a registered Danfoss trademark 65
10
10