Power [kW] Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A2 0-75-4.0 gG-10 gG-25 PKZM0-25 25
A3 5.5-7.5 gG-10 (5.5)
gG-16 (7.5)
gG-32 PKZM0-25 25
B3 11-15 gG-25 (11)
gG-32 (15)
gG-63 PKZM4-50 50
B4 18.5-30 gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-125 NZMB1-A100 100
C3 37-45 gG-63 (37)
gG-100 (45)
gG-150 NZMB2-A200 150
C4 55-75 aR-160 (55)
aR-200 (75)
aR-250 NZMB2-A250 250
A5 0.75-7.5 gG-10 (0.75-5.5)
gG-16 (7.5)
gG-32 PKZM0-25 25
B1 11-18 gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-80 PKZM4-63 63
B2 22-30 gG-50 (22)
gG-63 (30)
gG-100 NZMB1-A100 100
C1 37-55 gG-63 (37)
gG-100 (45)
aR-160 (55)
gG-160 (37-45)
aR-250 (55)
NZMB2-A200 160
C2 75 aR-200 (75) aR-250 NZMB2-A250 250
Table 10.16 525-600 V, Frame Sizes A, B and C
Enclosure
size
Power [kW] Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Moeller
Max trip level [A]
A3 1.1
1.5
2.2
3
4
5.5
7.5
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
- -
B2 11
15
18
22
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63 - -
C2 30
37
45
55
75
gG-63 (30)
gG-63 (37)
gG-80 (45)
gG-100 (55)
gG-125 (75)
gG-80 (30)
gG-100 (37)
gG-125 (45)
gG-160 (55-75)
- -
C3 37
45
gG-80
gG-100
gG-100
gG-125
- -
Table 10.17 525-690 V, Frame Sizes A, B and C
Specifications
VLT
®
AutomationDrive Operating
Instructions
MG33AM02 - VLT
®
is a registered Danfoss trademark 85
10
10

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
EnclosureIP20
ApprovalscUL, UL, CE
EMC filterBuilt-in
Communication OptionsCANopen, PROFIBUS DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit