42-3* General
Parameter Options/Valid
range
Default value Description Conversion
index
Data type
42-30 External Failure
Reaction
[0] STO [0] STO Select a safety function that is executed in case
of an external error.
- u_int8
42-31 Reset Source
[0] Drive Reset
[1] Drive Safe
Reset
[2] Safe Option
DI2_A
[0] Drive Reset Select the source that triggers the safety option
reset.
[0] Drive Reset - - the reset sources are:
•
The frequency converter Reset key on the
LCP.
•
The frequency converter digital input.
•
The reset signal via a fieldbus.
If there is an active alarm on the frequency
converter, the first reset signal resets the
frequency converter, and the second signal
resets the safety option.
[1] Drive Safe Reset - the reset sources are:
•
The frequency converter’s digital input. Select
option [100] Safe Option Reset on 1 of the
digital inputs for this source type to work.
•
The reset signal via a fieldbus. For the
fieldbus reset to work, set 8-14 Configurable
Control Word CTW to [3] Safe Option Reset.
The reset signal resets only the safety option.
[2] Safe Option DI2_A - the reset source is the
digital input DI2_A on the safety option. The
reset signal resets only the safety option.
-
u_int8
42-33 Parameter Set
Name
Visible String,
length: 8
SafeSet1 Enter the name of the safety parameter set (8
characters). Use this parameter to identify the
safety configurations.
- Visible-
String
Table 7.2 42-3* General
Parameter Set-up Operating Instructions
MG37F102 Danfoss A/S © 10/2014 All rights reserved. 27
7 7