7.9 Airow for Enclosures E1–E2 and F1–F13
e30bg051.10
1
2
1
Front channel airow, 340 m
3
/hr (200 cfm)
2 Back-channel airow,
1105 m
3
/hr (650 cfm) or 1444 m
3
/hr (850 cfm)
Illustration 7.2 Airow for Enclosure E1
e30bg052.10
1 2
1
Front channel airow, 255 m
3
/hr (150 cfm)
2 Back-channel airow,
1105 m
3
/hr (650 cfm) or 1444 m
3
/hr (850 cfm)
Illustration 7.3 Airow for Enclosure E2
Specications Design Guide
MG16C302 Danfoss A/S © 11/2017 All rights reserved. 65