7.3 Mains Supply
Mains supply
Supply terminals (6-pulse) L1, L2, L3
Supply terminals (12-pulse) L1-1, L2-1, L3-1, L1-2, L2-2, L3-2
Supply voltage 380–480 V ±10%, 525–690 V ±10%
Mains voltage low/mains voltage drop-out:
During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop
level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be
expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive.
Supply frequency 50/60 Hz ±5%
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
1)
True power factor (λ) 0.9 nominal at rated load
Displacement power factor (cos Φ) near unity (>0.98)
Switching on input supply L1, L2, L3 (power ups) Maximum 1 time/2 minute
Environment according to EN60664-1 Overvoltage category III/pollution degree 2
The drive is suitable for use on a circuit capable of delivering up to 100 kA short-circuit current rating (SCCR) at 480/600 V.
1) Calculations based on UL/IEC61800-3.
7.4 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–590 Hz
1)
Switching on output Unlimited
Ramp times 0.01–3600 s
1) Dependent on voltage and power.
Torque characteristics
Starting torque (constant torque) Maximum 150% for 60 s
1), 2)
Overload torque (constant torque) Maximum 150% for 60 s
1), 2)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
7.5 Ambient Conditions
Environment
E1/F1/F2/F3/F4/F8/F9/F10/F11/F12/F13 enclosures IP21/Type 1, IP54/Type 12
E2 enclosure IP00/Chassis
Vibration test 1.0 g
Relative humidity 5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H
2
S test Class Kd
Aggressive gases (IEC 60721-3-3) Class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at SFAVM switching mode)
- with derating Maximum 55 °C (131 °F)
1)
- with full output power of typical EFF2 motors (up to 90% output current) Maximum 50 °C (122 °F)
1)
- at full continuous FC output current Maximum 45 °C (113 °F)
1)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (13 to 149/158 °F)
Maximum altitude above sea level without derating 1000 m (3281 ft)
Maximum altitude above sea level with derating 3000 m (9842 ft)
1) For more information on derating, see chapter 9.6 Derating.
Specications
VLT
®
HVAC Drive FC 102
60 Danfoss A/S © 11/2017 All rights reserved. MG16C302
77

Table of Contents

Other manuals for Danfoss Metasys N2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Metasys N2 and is the answer not in the manual?

Danfoss Metasys N2 Specifications

General IconGeneral
BrandDanfoss
ModelMetasys N2
CategoryDC Drives
LanguageEnglish

Related product manuals