Binary Inputs (BI), continued..
NPA Unit Description Range FC Par. Number
48 31 Reserved
Par. 16-90 Alarm Word
49 30 Reserved
50 29 Drive Initialized 0=OK, 1=Alarm
51 28 Option Change 0=OK, 1=Alarm
52 27 Brake IGBT 0=OK, 1=Alarm
53 26 Brake Resistor 0=OK, 1=Alarm
54 25 1.8V Supply Low 0=OK, 1=Alarm
55 24 Mains Failure 0=OK, 1=Alarm
56 23 24V Supply Low 0=OK, 1=Alarm
57 22 Fieldbus Fault 0=OK, 1=Alarm
58 21 W Phase Loss 0=OK, 1=Alarm
59 20 V Phase Loss 0=OK, 1=Alarm
60 19 U Phase Loss 0=OK, 1=Alarm
61 18 Brake Overload 0=OK, 1=Alarm
62 17 Internal Fault 0=OK, 1=Alarm
63 16 Live Zero Error 0=OK, 1=Alarm
64 15 AMA not ok 0=OK, 1=Alarm
65 14 Mains Phase Loss 0=OK, 1=Alarm
66 13 Inrush Fault 0=OK, 1=Alarm
67 12 Short Circuit 0=OK, 1=Alarm
68 11 DC Overvoltage 0=OK, 1=Alarm
69 10 DC Undervoltage 0=OK, 1=Alarm
70 9 Inverter Overload 0=OK, 1=Alarm
71 8 Motor ETR Overload 0=Trip, 1=Trip lock
72 7 Motor Thermal Overload 0=OK, 1=Alarm
73 6 Torque Limit 0=OK,1=Alarm
74 5 Over Current 0=OK,1=Alarm
75 4 Ctrl. Word Timeout 0=OK,1=Alarm
76 3 Ctrl. Card Temp 0=OK,1=Alarm
77 2 Earth Fault 0=OK,1=Alarm
78 1 Pwr. Card Temp 0=OK,1=Alarm
79 0 Brake check 0=OK,1=Alarm
80 31 0=FALSE, 1=TRUE
Par. 16-94 Ext. Status Word
81 30 0=FALSE, 1=TRUE
82 29 0=FALSE, 1=TRUE
83 28 0=FALSE, 1=TRUE
84 27 0=FALSE, 1=TRUE
85 26 0=FALSE, 1=TRUE
86 25 0=FALSE, 1=TRUE
87 24 0=FALSE, 1=TRUE
88 23 0=FALSE, 1=TRUE
89 22 0=FALSE, 1=TRUE
90 21 0=FALSE, 1=TRUE
91 20 0=FALSE, 1=TRUE
92 19 0=FALSE, 1=TRUE
93 18 0=FALSE, 1=TRUE
94 17 0=FALSE, 1=TRUE
95 16 0=FALSE , 1=TRUE
96 15 OVC Active 0=FALSE , 1=TRUE
97 14 Out of Speed Reange 0=Auto mode, 1=Hand mode