Binary Inputs (BI), continued..
NPA Unit Description Selection FC Par. Number
98 13 Braking 0=FALSE, 1=TRUE
Par. 16-94 Ext. Status Word
99 12 Braking Max 0=Remote ref., 1=Local ref.
100 11 Brake Check Ok 0=FALSE, 1=TRUE
101 10 Output Frequency Low 0=FALSE, 1=TRUE
102 9 Output Frequency High 0=FALSE, 1=TRUE
103 8 Output Current Low 0=FALSE, 1=TRUE
104 7 Output Current High 0=FALSE, 1=TRUE
105 6 Feedback Low 0=FALSE, 1=TRUE
106 5 Feedback High 0=FALSE, 1=TRUE
107 4 Catch Up 0=FALSE, 1=TRUE
108 3 Slow Down 0=FALSE, 1=TRUE
109 2 Start CW/CCW 0=FALSE, 1=TRUE
110 1 AMA Running 0=FALSE, 1=TRUE
111 0 Ramping 0=FALSE, 1=TRUE
112 9 Ramp 0=RAMP 1, 1=RAMP 2
Par. 16-00 Control Word
113 15 Reverse 0=No function, 1=reverse
114 14 Setup MSB 0=FALSE, 1=TRUE
115 13 Setup LSB 0=FALSE, 1=TRUE
116 12 Relay02 0=Relay04 off, 1=Relay04 on
117 11 Relay01 0=Relay01 off, 1=Relay01 on
118 10 Res., always 0 (data valid) 0=FALSE
119 8 Jog 0=No Function, 1=Jog
120 7 Reset 0=No Function, 1=Reset
121 6 Start 0=start, 1=stop
122 5 Freeze Output 0=Freeze output, 1=Ramping
123 4 Q-stop 0=Q-stop, 1=Ramping
124 3 Coast 0=Coasting, 1=no Coast
125 2 DC Brake 0=DC Brake, 1=Ramp stop
126 1 Preset ref. MSB 0=FALSE, 1=TRUE
127 0 Preset ref. LSB 0=FALSE, 1=TRUE
128 0 Terminal 33 0=FALSE, 1=TRUE
Par. 16-60 Digital Input
129 1 Terminal 32 0=FALSE, 1=TRUE
130 2 Terminal 29 0=FALSE, 1=TRUE
131 3 Terminal 27 0=FALSE, 1=TRUE
132 4 Terminal 19 0=FALSE, 1=TRUE
133 5 Terminal 18 0=FALSE, 1=TRUE
134 6 GPIO Term X30/2 0=FALSE, 1=TRUE
135 7 GPIO Term X30/3 0=FALSE, 1=TRUE
136 8 GPIO Terminal X30/4 0=FALSE, 1=TRUE