Binary Inputs (BI), continued..
NPA Unit Description
Selection
1)
FC Par. Number
150 10
ECB Manual Bypass
Override
0=FALSE, 1=TRUE
Par. 31-10 Bypass Status
Word
151 9 ECB External Interlock 0=FALSE, 1=TRUE
152 8 ECB M3 Contactor Fault 0=FALSE, 1=TRUE
153 7 ECB M2 Contactor Fault 0=FALSE, 1=TRUE
154 6 ECB Overload Trip 0=FALSE, 1=TRUE
155 5
ECB Motor Running from
Bypass/Drive
0=FALSE, 1=TRUE
156 4 ECB Reserved 0=FALSE, 1=TRUE
157 3 ECB Bypass Mode 0=FALSE, 1=TRUE
158 2
ECB Automatic Bypass
Mode
0=FALSE, 1=TRUE
159 1 ECB Drive Mode 0=FALSE, 1=TRUE
160 0 ECB Test Mode 0=FALSE, 1=TRUE
187 31 - 0=FALSE, 1=TRUE
Par. 16-95 Ext. Status Word
2
188 30 - 0=FALSE, 1=TRUE
189 29 - 0=FALSE, 1=TRUE
190 28 - 0=FALSE, 1=TRUE
191 27 - 0=FALSE, 1=TRUE
192 26 - 0=FALSE, 1=TRUE
193 25 Fire Mode 0=FALSE, 1=TRUE
194 24 Drive Bypass 0=FALSE, 1=TRUE
195 23 Running 0=FALSE, 1=TRUE
196 22 Sleep Boost 0=FALSE, 1=TRUE
197 21 Sleep 0=FALSE, 1=TRUE
198 20 Start Delay 0=FALSE, 1=TRUE
199 19 Start Applied 0=FALSE, 1=TRUE
200 18 Start 0=FALSE, 1=TRUE
201 17 Start Request 0=FALSE, 1=TRUE
202 16 Jog 0=FALSE, 1=TRUE
203 15 Jog Request 0=FALSE, 1=TRUE
204 14 Freeze Output 0=FALSE, 1=TRUE
205 13 Freeze Output Request 0=FALSE, 1=TRUE
206 12 Standby 0=FALSE, 1=TRUE
207 11 Stop 0=FALSE, 1=TRUE
208 10 DC Brake 0=FALSE, 1=TRUE
209 9 Quick Stop 0=FALSE, 1=TRUE
210 8 Drive Ready 0=FALSE, 1=TRUE
211 7 Control Ready 0=FALSE, 1=TRUE
212 6 Start Prevented 0=FALSE, 1=TRUE
213 5 Relay 123 Active 0=FALSE, 1=TRUE
214 4 Profibus OFF3 Active 0=FALSE, 1=TRUE
215 3 Profibus OFF2 Active 0=FALSE, 1=TRUE
216 2 Profibus OFF1 Active 0=FALSE, 1=TRUE
217 1 Auto/Hand 0=AUTO, 1=TRUE
218 0 OFF 0=AUTO, 1=TRUE
1)
The values in bold are the default values
Appendix