= factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
MG.60.B1.02 - VLT is a registered Danfoss trade mark
615 Fault log: Error code
(F. LOG: ERROR CODE)
Value:
[Index 1-10] Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason
why a trip (cut-out of the VLT frequency converter)
occurs.
10 [1-10] log values are stored.
The lowest log number [1] contains the latest/most
recently saved data value; the highest log number [10]
contains the oldest data value.
If there is a trip on the VLT 6000 HVAC, it is possible
to see its cause, the time and possibly the values for
output current or output voltage.
Description of choice:
Stated as an error code in which the number refers to
a table on page 100.
The fault log is
only reset after manual initialisation,
see page 73.
616 Fault log: Time
(F. LOG: TIME)
Value:
[Index 1-10] Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total
number of hours run in connection with the 10 latest
trips.
10 [1-10] log values are stored.
The lowest log number [1] contains the latest/most
recently saved data value, while the highest log
number [10] contains the oldest data value.
Description of choice:
The fault log is only reset after manual initialisation,
see page 73.
617 Fault log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
This parameter makes it possible to see the value at
which a trip occurred. The unit of the value depends
on the alarm active in parameter 615 Fault log: Error
code.
Description of choice:
The fault log is
only reset after manual initialisation,
see page 73.
618 Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 602 kWh counter.
Description of choice:
If Reset [1] has been selected and when the [OK] key
is pressed, the kWh counter of the VLT frequency
converter is reset. This parameter cannot be selected
via the serial port, RS 485.
NB!
When the [OK] key has been activated, the
reset has been carried out.
619 Reset of hours-run counter
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET) [0]
Reset (RESET COUNTER) [1]
Function:
Reset to zero of parameter 601 Hours-run.
Description of choice:
If Reset [1] has been selected and when the [OK] key
is pressed, parameter 601 Hours-run is reset. This
parameter cannot be selected via the serial port,
RS 485.
NB!
When the [OK] key has been activated, the
reset has been carried out.