Ordering guide
This section makes it easier for you to specify and
order a VLT 6000 HVAC.
■■
■■
■ Choice of frequency converter
The frequency converter should be chosen on the
basis of the given motor current at maximum load on
the system. The rated output current I
VLT,N
must be
equal to or higher than the required motor current.
VLT 6000 HVAC is available for two mains voltage
ranges: 200-240 V and 380-460 V.
Mains voltage 200 - 240 V
Typical shaft output Max continuous output current Max continuous output power
P
VLT,N
I
VLT,N
at 240 V S
VLT,N
VLT
type [kW] [HP] [A] [kVA]
6002 1.1 1.5 6.6 2.7
6003 1.5 2.0 7.5 3.1
6004 2.2 3.0 10.6 4.4
6005 3.0 4.0 12.5 5.2
6006 4.0 5.0 16.7 6.9
6008 5.5 7.5 24.2 10.1
6011 7.5 10 30.8 12.8
6016 11 15 46.0 19.1
6022 15 20 59.4 24.7
6027 18.5 25 74.8 31.1
6032 22 30 88.0 36.6
6042 30 40 115/104* 43.2
6052 37 50 143/130* 54.0
6062 45 60 170/154* 64.0
■■
■■
■ Mains voltage
Choose mains voltage for 50/60 Hz:
- 200-240 V three-phase AC voltage
- 380-460 V three-phase AC voltage
* The first figure is for a motor voltage of 200-230 V.
The next figure is for a motor voltage of 231-240 V.