EasyManuals Logo

Danfoss VLT AAF006 Service Manual

Danfoss VLT AAF006
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
7.2.6 AC Capacitors
130BX438.10
1
2
3
4
5
6
7
8
Figure 7.4 AC Capacitors and AC Contactors
1
AC contactor 5 Auxiliary contactor
2 AC contactor terminal bracket 6 Line power contactor terminal (U, V, W)
3 AC contactor terminal bracket retaining nut 7 AC capacitor
4 AC contactor mounting screw 8 AC capacitor retaining nut (top)
Table 7.4
1. Remove the control assembly support bracket in
accordance with the procedure.
2. Remove the power card mounting plate in
accordance with the procedure.
3. Remove the nut (0.43 in [11 mm]) from each side
of the AC capacitor and the lug wires.
4. Remove the AC capacitor by cutting the cable tie
securing the AC capacitor.
Reinstall in the reverse order of this procedure. See
Table 1.7 for torque tightening values.