1
F2
2
130BA659.10
F4
Illustration 4.5 1: Main Load Carrying Points 2: Main Load Carrying Points
NOTE
The plinth is provided in the same packaging as the
frequency converter but is not attached to frame sizes F1-F4
during shipment. The plinth is required to allow airflow to
the frequency converter to provide proper cooling. The F
frames should be positioned on top of the plinth in the final
installation location. The angle from the top of the frequency
converter to the lifting cable should be 60° or greater.
A spreader bar is an acceptable way to lift the F Frame.
How to Install
VLT
®
Active Front End AFE 302 Operating Instructions Liebherr
MG.33.X2.02 - VLT
®
is a registered Danfoss trademark 25
4 4