Alarm Word Extended Status Word
Bit Hex Dec Alarm Word Alarm Word 2 Warning Word Warning
Word 2
Extended
Status Word
0 00000001 1 ServiceTrip, Read/
Write
reserved Ramping
1 00000002 2 Heatsink temp. (A29) ServiceTrip,
(reserved)
Heatsink temp. (W29) reserved
2 00000004 4 Earth Fault (A14) ServiceTrip,
Typecode/
Sparepart
Earth Fault (W14) reserved
3 00000008 8 Ctrl.Card Temp (A65) ServiceTrip,
(reserved)
Ctrl.Card Temp (W65) reserved
4 00000010 16 Ctrl. Word TO (A17) ServiceTrip,
(reserved)
Ctrl. Word TO (W17)
5 00000020 32 Over Current (A13) reserved Over Current (W13) reserved
6 00000040 64 reserved reserved
7 00000080 128 reserved reserved
8 00000100 256 reserved reserved
9 00000200 512 Inverter Overld. (A9) reserved Inverter Overld (W9) reserved
10 00000400 1024 DC under Volt (A8) reserved DC under Volt (W8)
11 00000800 2048 DC over Volt (A7) reserved DC over Volt (W7)
12 00001000 4096 Short Circuit (A16) reserved DC Voltage Low (W6) reserved
13 00002000 8192 Inrush Fault (A33) reserved DC Voltage High (W5)
14 00004000 16384 Mains ph. Loss (A4) reserved
15 00008000 32768 reserved
16 00010000 65536 reserved
17 00020000 131072 Internal Fault (A38) 10V Low (W1) Password Timelock
18 00040000 262144 Fans error Fans Warn Password Protection
19 00080000 524288
20 00100000 1048576 reserved reserved
21 00200000 2097152 reserved reserved
22 00400000 4194304 Fieldbus Fault (A34) reserved Fieldbus Fault (W34) reserved
23 00800000 8388608 24 V Supply Low
(A47)
reserved 24V Supply Low (W47) reserved
24 01000000 16777216 Mains Failure (A36) reserved Mains Failure (W36) reserved
25 02000000 33554432 1.8V Supply Low
(A48)
reserved Current Limit (W59) reserved
26 04000000 67108864 reserved Low Temp (W66) reserved
27 08000000 134217728 reserved Voltage Limit (W64) reserved
28 10000000 268435456 Option Change (A67) reserved reserved
29 20000000 536870912 AFE Initialized(A80) Feedback Fault
(A61, A90)
Feedback Fault (W61, W90)
30 40000000 1073741824 Safe Stop (A68)
31 80000000 2147483648 Extended Status Word
Table 5.4 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words
can be read out via serial bus or optional fieldbus for
diagnose. See also 16-94 Ext. Status Word.
WARNING 1, 10 Volts low:
The 10V voltage from terminal 50 on the control card is
below 10V.
Remove some of the load from terminal 50, as the 10V
supply is overloaded. Max. 15 mA or minimum 590 Ω.
WARNING 5, DC link voltage high:
The DC bus voltage is higher than the overvoltage limit of
the control system. The AFE is still active.
WARNING 6, DC link voltage low
The DC bus voltage is below the undervoltage limit of the
control system. The AFE is still active.