EasyManua.ls Logo

Danfoss VLT AFE 302 - Parameters: 0-** Operation and Display

Danfoss VLT AFE 302
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 Parameters: 0-** Operation and Display
Parameters related to the basic functionality of the AFE.
Parameters related to the function of the display and
buttons.
5.2.1 0-0* Basic Settings
0-01 Language
Option: Function:
Defines the language to be used in the display.
[0] * English Part of Language packages 1 - 4
5.2.2 0-1* Set-up Operations
Define and control the individual parameter setups.
0-10 Active Set-up
Option: Function:
Select the set-up to control the frequency
converter functions.
[0] Factory
setup
Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a known
state.
[1] * Set-up 1
Set-up 1 [1] to Set-up 4 [4] are the four separate
parameter set-ups within which all parameters
can be programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up Remote selection of set-ups using digital
inputs and the serial communication port. This
set-up uses the settings from 0-12 This Set-up
Linked to. Stop the frequency converter before
making changes to open- and closed loop
functions
Required to use emergency mode.
0-11 Edit Set-up
Option: Function:
Editing can either follow the active setup
selection (par. 0-10), or be fixed at a setup
number. This parameter is unique for LCP and
buses.
[0] Factory setup
[1] * Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Active Set-up
0-12 This Set-up Linked to
Option: Function:
This parameter sets the AFE to automatically
synchronise the values of the 'not changeable
during operation' parameters between this set-
up and the set-up selected in this parameter.
Note: The values in this setup are overwritten.
[0] * Not linked
[1] Set-up 1
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range: Function:
0
N/
A*
[0 -
255
N/
A]
View a list of all the set-ups linked by means of 0-12 This
Set-up Linked to. The parameter has one index for each
parameter set-up. The parameter value displayed for
each index represents which setups are linked to that
parameter setup.
Index LCP value
0 {0}
1 {1,2}
2 {1,2}
3 {3}
4 {4}
Table 5.2 Example: Set-up 1 and Set-up 2 are linked
0-14 Readout: Edit Set-ups / Channel
Range: Function:
0* [-2147483648 -
2147483647 ]
View the setting of 0-11 Edit Set-up for each
of the four different communication
channels. When the number is displayed in
hex, as it is in the LCP, each number
represents one channel.
Numbers 1-4 represent a set-up number; ‘F’
means factory setting; and ‘A’ means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1-5.
Example: The number AAAAAA21h means
that the FC bus selected Set-up 2 in 0-11 Edit
Set-up, the LCP selected Set-up 1 and all
others used the active set-up.
How to Programme
VLT
®
Active Front End AFE 302 Operating Instructions Liebherr
34 MG.33.X2.02 - VLT
®
is a registered Danfoss trademark
55

Table of Contents

Related product manuals