5.10 Parameters: 40-** Mains / Filter
5.10.1 40-0* Mains Data
40-00 Mains Voltage
Range: Function:
630 V* [[525-690 V]] Set the mains voltage line to line.
40-01 Mains Frequency
Option: Function:
[0] * 50 Hz Set the mains nominal frequency.
[1] 60 Hz
40-02 Mains Inductance
Range: Function:
0.039 mH* [0.000 - 65.000
mH]
Set the Inductance of the mains.
This could be the transformer.
40-03 Mains Resistance
Range: Function:
0.50 mOhm* [0.00 - 650.00
mOhm]
Set the value of the mains
resistance. This could be the
transformer.
5.10.2 40-1* LCL Filter
40-10 Mains Side Inductance (Lm)
Range: Function:
0.029 mH* [0.000 - 65.000 mH] Set the main side inductance of
the LCL filter.
40-11 Mains Side Resistance
Range: Function:
0.19 mOhm* [0.00 - 650.00
mOhm]
Set the main side resistance
of the LCL filter.
40-12 Converter Side Inductance (LC)
Range: Function:
0.100 mH* [0.000 - 65.000 mH] Set the converter side
inductance of the LCL filter.
40-13 Converter Side Resistance (RC)
Range: Function:
0.48 mOhm* [0.00 - 650.00
mOhm]
Set the converter side
resistance of the LCL filter.
40-14 Filter Capacity
Range: Function:
400 uF* [0 - 65000 uF] Set the capacity of the LCL filter.