3.8 System Start-up
The procedure in this section requires user-wiring and
application programming to be completed. 6 Application
Set-up Examples is intended to help with this task. Other
aids to application set-up are listed in 1.2 Additional
Resources. The following procedure is recommended after
application set-up by the user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any condition. Failure
to do so could result in personal injury or equipment
damage.
1. Press [Auto On].
2. Ensure that external control functions are
properly wired to the adjustable frequency drive
and all programming completed.
3. Apply an external run command.
4. Adjust the speed reference throughout the speed
range.
5. Remove the external run command.
6. Note any problems.
If warnings or alarms occur, see 8 Warnings and Alarms.
3.9
Acoustic Noise or Vibration
If the motor or the equipment driven by the motor, e.g., a
fan blade, is making noise or vibrations at certain
frequencies, try the following:
Speed Bypass, parameter group 4-6*
Overmodulation, 14-03 Overmodulation set to off
Switching pattern and switching frequency
parameter group 14-0*
Resonance Dampening, 1-64 Resonance
Dampening
Start-up and Functional Tes...
VLT
®
AQUA Drive
Instruction Manual
MG20M922 - VLT
®
is a registered Danfoss trademark 3-7
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals